KETHANA ENCLAVE APARTMENT OWNER'S ASSOCIATION
Update - Dt: 23rd February 2010
Rs. 4,100/- towards the Electricity Inspection charges has been paid on 23/02/ 2010 and we have received the acknowledgement.
NOW WE NEED TO FOCUS ON FIXING THE BELOW DEFECTS (Extracted from the Inspection Report). And we need to complete these within 15 days from the date of inspection (19/02/2010).
1. DG SET
- All Sundry and combustible material in the switch gear room/generator room shall be removed.
- Full length MV grade rubber mats shall be spread in front of all LT panels, DG panel boards.
- Instruction chart for restoration of person suffering from electric shock shall be displayed at conspicuous position at switch gear room/ generator room.
- Fire extinguisher suitable for electrical fire shall be made available in switch gear/generator room.
- Approved drawing and List of Authorised persons of your electrical installation under direct supervision of person holding competent permit issued by this department shall be exhibited in the switch gear room/ generator room.
- Cable glands shall be earthed.
- Earth electrodes shall be placed, reconstructed and maintained as per ISS 3043-1987.
- Energy meter and current transformers provided for DG set shall be got calibrated and test report shall be furnished.
- B & D statement for the units generated from the DG set shall be sent to this office regularly with in 5th of every month, failing which penalty of Rs. 500/- per month will be levied.
- Generator log book shall be maintained duly recording Generated units and shall be kept open at the time of inspection by inspecting authorities.
- Earth test results of all the earth pits shall be furnished.
- Approval copy of the DG set shall be produced. (Lifts)
2. LIFTS
- Lift Governor shall be got tested for its satisfactory operation from the lift agency and test report shall be furnished.
- Floor numbers shall be marked at each floor opposite to the lift car.
- Way of Lift Machine Room shall be marked soon after the last landing.
- Exhaust fan shall be in the lift machine room. (Not working, shall be repaired)
- Trained lift operator shall be appointed and the names of operators shall be provided to this office.